Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1657274.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,929.00
Current Penalty: $6,000.00
Issuance Date: 09/05/2023
Nr Instances: 3
Nr Exposed: 2
Abatement Date: 10/23/2023
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 09/27/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/27/2023 | $6,000.00 | 10/23/2023 | Serious | |
| Penalty | Z: Issued | 09/05/2023 | $8,929.00 | 10/23/2023 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: On or about March 13, 2023, and at times prior thereto, employees operating electrical equipment of 480V while a depth of working space was not provided, exposing employees to electrical shock hazards.