Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 1634344.015
Citation: 01006
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $4,687.00
Current Penalty: $0.00
Issuance Date: 05/09/2023
Nr Instances: 2
Nr Exposed: 11
Abatement Date: 06/05/2023
Gravity: 1
Report ID: 0213900
Contest Date:
Final Order: 06/06/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/06/2023 | $0.00 | 06/05/2023 | Other | |
Penalty | Z: Issued | 05/09/2023 | $4,687.00 | 06/05/2023 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: a) Production floor next to chemical baths: The space in front of a 480 volt electrical panel that powered the overhead lights and ventilation was used to store pallets of metal pieces in various stages of production. Observed on or about 11/16/22. b)Production floor in front of paint shop: The space in front of a 480 volt electrical panel that powered the overhead lights was used to store a cart used to transport product around the floor. Observed on or about 11/16/22. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.