Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 1608381.015
Citation: 01006
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $11,167.00
Current Penalty: $11,167.00
Issuance Date: 01/12/2023
Nr Instances: 6
Nr Exposed: 33
Abatement Date: 02/23/2023
Gravity: 10
Report ID: 1032100
Contest Date: 02/09/2023
Final Order: 08/07/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/07/2023 | $11,167.00 | 02/23/2023 | Serious | |
Penalty | C: Contested | 02/09/2023 | $11,167.00 | 02/23/2023 | Serious | |
Penalty | Z: Issued | 01/12/2023 | $11,167.00 | 02/23/2023 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxillary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: a) Stateroom 6 - On or about July 20, 20222, and times prior thereto, an outlet receptable installed for use had a damaged cover allowing for opening and was not effectively closed, exposing employees to electrical and fire hazards. b) Pump Room/Worktable - On or about September 29, 2022, and times prior thereto, openings were observed with knockouts missing for breaker spaces 5 and 7, exposing employees to electrical and fire hazards. c) Engine Room - On or about October 2, 2022, and times prior thereto, openings were observed with knockouts missing for breaker spaces 15, 17, and 19, exposing employees to electrical and fire hazards. d) Stateroom 2 - On or about October 25, 2022, and times prior thereto, a housing unit for a heater was observed with unused openings not effectively closed with a missing knockout and cover, exposing employees to electrical and fire hazards. e) Stateroom 2 - On or about October 25, 2022, and times prior thereto, a metal light housing permanently installed was observed with an unused opening at the socket, exposing employees to electrical hazards. f) Stateroom 8 - On or about October 25, 2022, and times prior thereto, a subpanel was observed with unused openings not effectively closed between the top and bottom of the cover, exposing employees to electrical hazards.