Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1582875.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,215.00
Current Penalty: $5,000.00
Issuance Date: 08/29/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 10/14/2022
Gravity: 1
Report ID: 0830500
Contest Date:
Final Order: 09/16/2022
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/16/2022 | $5,000.00 | 10/14/2022 | Serious | |
Penalty | Z: Issued | 08/29/2022 | $6,215.00 | 09/22/2022 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.303(g)(1)(i): Workspace was less than 3 feet in front of electric equipment operating at 600 volts nominal, or less: (a) On and before March 9, 2022, the employer did not maintain workspace of at least 3 feet in front of an electrical circuit breaker panel in the back storage room in that it was obstructed by product that was stacked in front of it. This condition exposed the employees to electrical hazards.