Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1450674.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,048.00
Current Penalty: $2,024.00
Issuance Date: 05/19/2020
Nr Instances: 5
Nr Exposed: 25
Abatement Date: 06/22/2020
Gravity: 1
Report ID: 0420600
Contest Date:
Final Order: 06/15/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/15/2020 | $2,024.00 | 06/22/2020 | Serious | |
Penalty | Z: Issued | 05/19/2020 | $4,048.00 | 06/22/2020 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about 12/12/2019, at the fabrication area near the MEP bending machines, employees were exposed to electrical hazards, in that, a breaker panel with 9 breakers did not have labels to indicate their purpose. b. On or about 12/12/2019, at the fabrication area S-11 column, employees were exposed to electrical hazards, in that, a breaker panel with 14 breakers did not have labels to indicate their purpose. c. On or about 12/12/2019, at the fabrication area S-11 column, employees were exposed to electrical hazards, in that, a breaker panel with 7 breakers did not have labels to indicate their purpose. d. On or about 12/12/2019, at the fabrication area S-17 column, employees were exposed to electrical hazards, in that, two main disconnects did not have labels to indicate their purpose. e. On or about 12/12/2019, at the fabrication area east wall S-21 column, employees were exposed to electrical hazards, in that, two breaker panes had a total of 15 breakers without a label to indicate their purpose.