Violation Detail
Standard Cited: 19100334 B01 Use of equipment.
Inspection Nr: 1419085.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/05/2019
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 09/11/2019
Gravity: 10
Report ID: 0213100
Contest Date:
Final Order: 10/01/2019
Related Event Code (REC): C
Emphasis:
| Failure to Abate | |||||||
|---|---|---|---|---|---|---|---|
| Activity Nr | Issuance | Penalty | Contest | Final Order | |||
| 1457723 | 04/15/2020 | $0.00 | 05/12/2020 | ||||
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| FTA | Z: Issued | 04/15/2020 | $0.00 | 1457723.015 | ||
| Penalty | Z: Issued | 09/05/2019 | $0.00 | 09/11/2019 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.334(b)(1): Load rated switches, circuit breakers or other devices specifically designed as disconnecting means were not used for the opening, reversing or closing of electric power and lighting circuits under load conditions: a) Facility - On or prior to July 30, 2019, employees were exposed to electrical hazards due to flipping a circuit breaker(s) on/off in a 110 Volt Electrical Panel to turn the lights on/off on a daily basis. The circuit breaker(s) being used to turn the lights on/off were not designed to be used as light switch.