Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1278776.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,934.00
Current Penalty: $9,700.50
Issuance Date: 05/07/2018
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 05/11/2018
Gravity: 10
Report ID: 0213100
Contest Date: 06/05/2018
Final Order: 08/31/2018
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/31/2018 | $9,700.50 | 05/11/2018 | Serious | |
Penalty | C: Contested | 06/06/2018 | $12,934.00 | 05/11/2018 | Serious | |
Penalty | Z: Issued | 05/07/2018 | $12,934.00 | 05/11/2018 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.307(c): Equipment, wiring and installations of equipment in hazardous (classified) locations was not intrinsically safe, approved, or safe for Class 1/Division 2 hazardous (classified) locations: a) Batching Area in the Main Building Addition - On November 20, 2017, and at times prior, the employer used standard electrical equipment and electrical wiring such as but not limited to outlets, lighting, the drum lifter and electrical panels within the batching area. The employer transferred category 2 flammable liquids such as but not limited to Hexamethyldisiloxne and Isopar "C", in this area it was thus a Class 1 Division 2 location.