Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1187121.015
Citation: 01006
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $9,959.00
Current Penalty: $12,500.00
Issuance Date: 04/12/2017
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC):
Gravity: 5
Report ID: 0523400
Contest Date: 05/02/2017
Final Order: 04/26/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/26/2018 | $12,500.00 | Serious | ||
Penalty | C: Contested | 05/03/2017 | $9,959.00 | Serious | ||
Penalty | Z: Issued | 04/12/2017 | $9,959.00 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flash point below 100 °F (37.8 °C), were dispensed into containers where the nozzle and container were not electrically interconnected: (a) On or about October 27, 2016, in the flammable storage room: Acetone was dispensed into containers for use throughout the facility from two (2) 55 gallon drums. Both of the drums of acetone were not grounded and when acetone was dispensed into smaller containers, no bonding wire was used.