Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1167646.015
Citation: 01006
Citation Type: Serious
Abatement Date: 03/02/2017 2
Initial Penalty: $9,959.00
Current Penalty: $6,600.00
Issuance Date: 02/01/2017
Nr Instances: 2
Nr Exposed: 2
Related Event Code (REC): C
Gravity: 5
Report ID: 0523300
Contest Date: 02/21/2017
Final Order: 02/08/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/08/2018 | $6,600.00 | 03/02/2017 | Serious | |
Penalty | C: Contested | 02/23/2017 | $9,959.00 | 03/02/2017 | Serious | |
Penalty | Z: Issued | 02/01/2017 | $9,959.00 | 03/02/2017 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.307(c)(2)(i): Equipment shall be approved not only for the class of location, but also for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that will be present. Note to paragraph (c)(2)(i) of this section: NFPA 70, the National Electrical Code, lists or defines hazardous gases, vapors, and dusts by "Groups" characterized by their ignitable or combustible properties. On or about August 8, 2016, electrical equipment in the Cured in Place Pipe (CIPP) area where flammable liquids was present in totes for testing in the closed Cured-In-Place-Pipe process system, was not approved for the ignitable or combustible properties of that liquid in the event of a tote rupture or breakdown.