Violation Detail
Standard Cited: 19100252 C02 II General requirements.
Inspection Nr: 1155212.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,224.00
Current Penalty: $2,100.00
Issuance Date: 12/06/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 04/20/2017
Gravity: 10
Report ID: 0111100
Contest Date: 12/29/2016
Final Order: 01/22/2018
Related Event Code (REC):
Emphasis:
Substance: 0689
Substance: 0691
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/22/2018 | $2,100.00 | 04/20/2017 | Serious | |
Penalty | C: Contested | 01/03/2017 | $11,224.00 | 04/20/2017 | Serious | |
Penalty | Z: Issued | 12/06/2016 | $11,224.00 | 04/20/2017 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.252(c)(2)(ii): Mechanical ventilation provided did not meet the minimum rate of 2,000 cubic feet (57 m3) per minute per welder: Maintenance Garage - On or about June 22, 2016, mechanical ventilation provided by the window fan was operating at 321 cubic feet per minute and did not meet the minimum rate of 2,000 cubic feet per minute per welder.