Violation Detail
Standard Cited: 19100146 D03 IV Permit-required confined spaces
Inspection Nr: 1404889.015
Citation: 01005E
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/15/2019
Nr Instances: 1
Nr Exposed: 15
Abatement Date: 06/30/2020
Gravity: 10
Report ID: 0522300
Contest Date:
Final Order: 12/10/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 03/13/2020 | $0.00 | 06/30/2020 | Serious | |
Penalty | I: Informal Settlement | 12/10/2019 | $0.00 | 01/10/2020 | Serious | |
Penalty | Z: Issued | 11/15/2019 | $0.00 | 12/12/2019 | Serious |
Text For Citation: 01 Item/Group: 005E Hazard:
29 CFR 1910.146(d)(3)(iv): Under the permit space program required by 29 CFR 1910.146(c)(4), the employer did not develop and implement the means, procedures, and practices necessary for safe permit space entry operations, including, but not limited to purging, inerting, flushing, or ventilating the permit space as necessary to eliminate or control atmospheric hazards. a) On or about May 31, 2019, weld box vessel #1 in the Melt Shop #1 was entered by an employee during cleaning operations without a full permit entry. The employer's program did not require steps to ensure that hazardous accumulations of combustible metal residues on the interior of the vessel were removed prior to entry or otherwise prevented from generating dense cloud form during cleaning methods which utilized techniques such as, but not limited to, sweeping, compressed air, and/or chipping. b) On or about May 31, 2019, weld box vessel #2 in the Melt Shop #1 was entered by an employee during cleaning operations without a full permit entry. The employer's program did not require steps to ensure that hazardous accumulations of combustible metal residues on the interior of the vessel were removed prior to entry or otherwise prevented from generating dense cloud form during cleaning methods which utilized techniques such as, but not limited to, sweeping, compressed air, and/or chipping. c) On or about May 31, 2019, weld box vessel #3 in the Melt Shop #1 was entered by an employee during cleaning operations without a full permit entry. The employer's program did not require steps to ensure that hazardous accumulations of combustible metal residues on the interior of the vessel were removed prior to entry or otherwise prevented from generating dense cloud form during cleaning methods which utilized techniques such as, but not limited to, sweeping, compressed air, and/or chipping. d) On or about May 31, 2019, weld box vessel #4 in the Melt Shop #1 was entered by an employee during cleaning operations without a full permit entry. The employer's program did not require steps to ensure that hazardous accumulations of combustible metal residues on the interior of the vessel were removed prior to entry or otherwise prevented from generating dense cloud form during cleaning methods which utilized techniques such as, but not limited to, sweeping, compressed air, and/or chipping. e) On or about May 31, 2019, weld box vessel #5 in the Melt Shop #1 was entered by an employee during cleaning operations without a full permit entry. The employer's program did not require steps to ensure that hazardous accumulations of combustible metal residues on the interior of the vessel were removed prior to entry or otherwise prevented from generating dense cloud form during cleaning methods which utilized techniques such as, but not limited to, sweeping, compressed air, and/or chipping.