Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1285551.015
Citation: 01005D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,315.00
Current Penalty: $0.00
Issuance Date: 04/02/2018
Nr Instances: 5
Nr Exposed: 4
Abatement Date: 06/07/2018
Gravity: 5
Report ID: 0626700
Contest Date:
Final Order: 04/26/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/26/2018 | $0.00 | 06/07/2018 | Serious | |
Penalty | Z: Issued | 04/02/2018 | $8,315.00 | 05/07/2018 | Serious |
Text For Citation: 01 Item/Group: 005D Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) In the production area, where the temporary flexible cord used to supply electrical power to the Oddy Novatek 2 machine was not equipped with a strain relief which exposed the employees to electrical hazards. b) In the production area, where the temporary flexible cord used to supply electrical power to the dough cutting machine was not equipped with a strain relief which exposed the employees to electrical hazards. c) In the production area, where the temporary flexible cords used to supply electrical power to the vertical floor mixing machines were not equipped with a strain reliefs which exposed the employees to electrical hazards. d) In the production area adjacent to the vertical floor mixers, where the temporary flexible cord was used to supply electrical power to the horizontal mixing machine was not equipped with a strain relief which exposed the employees to electrical hazards. e) In the production area, where the temporary flexible cord was used to supply electrical power to the loafing machine was not equipped with a strain relief which exposed the employees to electrical hazards.