Violation Detail
Standard Cited: 19100107 L07 V Spray finishing using flammable and combustible materials.
Inspection Nr: 898505.015
Citation: 01005C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/06/2013
Nr Instances: 5
Nr Exposed: 50
Abatement Date: 01/15/2014
Gravity: 5
Report ID: 0521700
Contest Date:
Final Order: 09/13/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/13/2013 | $0.00 | 01/15/2014 | Serious | |
| Penalty | Z: Issued | 09/06/2013 | $0.00 | 10/24/2013 | Serious |
Text For Citation: 01 Item/Group: 005C Hazard:
29 CFR 1910.107(l)(7)(v): The electrical equipment shall be so interlocked with the ventilation system that the equipment cannot be operated unless the ventilation fans are in operation. a. On or about April 1, 2013, employees working in the two (2) powder coating touch up areas, were required to spray combustible powder while utilizing hand and/or electrostatic spraying equipment. An interlock was not installed in the powder coating touch up(s), which prevented electrical equipment from operation without the ventilation system in operation. Employees were thereby exposed to hazards associated with fires and explosions.
Translate