Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1568845.015
Citation: 01005C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/09/2022
Nr Instances: 1
Nr Exposed: 62
Abatement Date: 01/31/2023
Gravity: 10
Report ID: 0112300
Contest Date:
Final Order: 07/05/2022
Related Event Code (REC): R
Emphasis:
Substance: E200
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 10/28/2022 | $0.00 | 01/31/2023 | Serious | |
Penalty | I: Informal Settlement | 07/05/2022 | $0.00 | 10/31/2022 | Serious | |
Penalty | Z: Issued | 06/09/2022 | $0.00 | 07/27/2022 | Serious |
Text For Citation: 01 Item/Group: 005C Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of dust, that was or could be present: (a) Other Production and Storage Areas: On or about December 10, 2021, employees were working in an area with buildup of combustible dust where there were open motor fans, electrical outlet boxes, breaker panels, disconnect switches, normal lighting snap switches, overhead lighting, and control panels within a Class II, Division 2, location which were not intrinsically safe and were not approved for a Class II, Division 2 location or safe for Class II, Division 2 locations. (b) Other Production and Storage Areas: On or about December 10, 2021, a vacuum used in a Class II, Division 2 location was not intrinsically safe, approved for the Class II, Division 2 location or safe for Class II, Division 2 locations.