Violation Detail
Standard Cited: 19100303 B07 General.
This violation item has been deleted.
Inspection Nr: 1564425.015
Citation: 01005C
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/27/2022
Nr Instances: 3
Nr Exposed: 6
Abatement Date: 05/23/2022
Gravity: 10
Report ID: 0317500
Contest Date:
Final Order: 05/20/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/20/2022 | $0.00 | 05/23/2022 | Serious | |
Penalty | Z: Issued | 04/27/2022 | $0.00 | 05/23/2022 | Serious |
Text For Citation: 01 Item/Group: 005C Hazard:
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: a) Jobsite, Mixing Area, 301 Brickyard Road, Clairton, PA 15025: Observed on or about November 18, 2021, an electrical cabinet containing high voltage (480 volt) power was left open. Three electrical cables (one for the Press 1 feeder, one for the brick crusher machine, and one for the hydraulic plunger) were connected to the inside of the cabinet. Two of the cables prevented the cabinet door from being able to close. The flexible cable (220 volt) leading to the brick crusher was draped over the floor and not protected from being damaged or snagged by forklifts used to remove bags from the bottom of the brick crusher. b) Jobsite, Lance Shed, 301 Brickyard Road, Clairton, PA 15025: Observed on or about November 23, 2021, the electrical panel (220 Volt) marked '1' to the left of the Lance Shed entrance was left open and there was grey and blue duct tape over the bottom portion of the panel. c) Jobsite, Lance Shed, 301 Brickyard Road, Clairton, PA 15025: Observed on or about November 23, 2021, the electrical panel marked '2' to the left of the Lance Shed entrance was left open (the panel cover was missing) and there was grey duct tape covering the top portion of the panel.