Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 932343.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/20/2013
Nr Instances: 5
Nr Exposed: 2
Abatement Date: 10/25/2013
Gravity: 1
Report ID: 0215800
Contest Date: 11/01/2013
Final Order: 04/25/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 04/25/2014 | $0.00 | 10/25/2013 | Serious | |
| Penalty | C: Contested | 11/05/2013 | $0.00 | 10/25/2013 | Serious | |
| Penalty | Z: Issued | 09/20/2013 | $0.00 | 10/25/2013 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Shipping/Receiving Area, on or about 8/20/13: An extension cord for a bug zapper was strung overhead and being used as permanent wiring. b) Shipping/Receiving Area, on or about 8/20/13: A strip outlet being used for charging screw gun batteries was being used as permanent wiring. c) RGA Area, on or about 8/20/13: A blue extension cord providing current to a Wells horizontal bandsaw was being used as permanent wiring. d) Advanced Air Area, on or about 8/20/13: An orange extension cord providing current to a belt sander and a bandsaw was being used as permanent wiring. e) Advanced Air Area, on or about 8/20/13: A flexible cord plugged into a four way receptacle outlet on the floor providing current to several outlets along two workbenches was being used as permanent wiring. f) Wine Work Cell, on or about 8/20/13: A strip outlet being used for charging batteries for portable tools was being used as permanent wiring. Abatement certification must be submitted for these items.
Translate