Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
Inspection Nr: 191250.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/07/2012
Nr Instances: 2
Nr Exposed: 450
Abatement Date: 08/28/2012
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 08/27/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/27/2012 | $0.00 | 08/28/2012 | Serious | |
| Penalty | Z: Issued | 08/07/2012 | $0.00 | 08/28/2012 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting: a) Ammonia Room - The door leading from the boiler room to the ammonia room was not self-closing per ANSI/ASHRAE Standard 15-2010 8.11.2. It was binding to the floor and had to be forcibly pulled closed. This was not addressed in the 2010 PHA. On or about 2/8/12. b) Ammonia Room, upper part of the east wall - The openings around an 8" water discharge pipe from the condensers to the freezers, and a branch water discharge pipe that passed through the wall to the adjacent production area through were not sealed per ANSI/ASHRAE Standard 15-2010 8.11.2. This was not addressed in the 2010 PHA. On or about 2/8/12. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.