Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1708799.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $0.00
Issuance Date: 04/09/2024
Nr Instances: 7
Nr Exposed: 20
Abatement Date: 07/10/2024
Gravity: 10
Report ID: 0625700
Contest Date:
Final Order: 06/28/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/28/2024 | $0.00 | 07/10/2024 | Serious | |
Penalty | Z: Issued | 04/09/2024 | $16,131.00 | 07/10/2024 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment. Instance a) On or about 11/07/2023, at No. 4 Crude unit, the employer did not perform inspections and tests on Pressure Indication Control or (Pressure indicator Controller) PIC-401 (P&ID 58-E-54-2003, No. 20). Instance b) On or about 11/07/2023, at No.1 Platformer unit, the employer did not perform inspections and tests on Hydrogen Low Flow Interlocks FT-7302B/C/D, (P&ID 18-E-54-1000, No. 16). Instance c) On or about 11/07/2023, at No.1 Platformer unit, the employer did not perform inspections and tests on Level Indication Control LIC-7303 (P&ID 18-E-54-3000, No. 21). Instance d) On or about 11/07/2023, at No.1 Platformer unit, the employer did not perform inspections and tests on High-High Level Alarm (High Level Shutdown Switch) LAHH-7351 for No. 1 Platform Product Separator 18-SE-01 (P&ID 18-E-54-3000, No. 21). Instance e) On or about 11/07/2023, at No.1 Platformer unit, the employer did not perform inspections and tests on Emergency Remote Shutdown HS-7370A of Platform East Compressor C-0010 (P&ID 18-E-54-5000G, No. 1). Instance f) On or about 11/07/2023, at No. 4 Crude unit, the employer did not perform inspections on Rupture Disc RD-58-03 (P&ID 58-E-54-4000, No. 33). Instance g) On or about 11/07/2023, at No. 4 Crude unit, the employer did not perform inspections on Rupture Disc RD-58-04 (P&ID 58-E-54-4000, No. 33).