Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1691967.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $0.00
Issuance Date: 02/07/2024
Nr Instances: 8
Nr Exposed: 3
Abatement Date: 05/07/2024
Gravity: 10
Report ID: 0627700
Contest Date:
Final Order: 03/07/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/07/2024 | $0.00 | 05/07/2024 | Serious | |
Penalty | Z: Issued | 02/07/2024 | $16,131.00 | 05/07/2024 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment in the following instances: a.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-32, Hansen, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. b.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-33, Hansen, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. c.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-36, Henry, 5600, 3/4x1, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. d.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-37, Hansen, H5600R, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. e.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-16, Hansen, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. f.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-17, Hansen, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. g.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-20, Parker, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards. h.) On August 18, 2023, and at times prior thereto, the employer did not perform inspection and tests on relief valves SRV-21, Hansen, H5600A, 1/2x3/4, set at 250psig. This condition exposes employees to potential anhydrous ammonia release hazards.