Violation Detail
Standard Cited: 19100303 B06 General.
Inspection Nr: 1674012.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/11/2023
Nr Instances: 1
Nr Exposed: 18
Abatement Date: 09/28/2023
Gravity: 1
Report ID: 0316700
Contest Date:
Final Order: 10/05/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/05/2023 | $0.00 | 09/28/2023 | Serious | |
Penalty | Z: Issued | 09/11/2023 | $0.00 | 09/28/2023 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures and were not identified for use in the operating environment: (a) Refrigeration machine (engine) room interior - On or about June 15, 2023 the electrical equipment such as the boxes, disconnect, heavy equipment outlet, and control panel were in immediate proximity to the emergency eyewash and drenching shower and were not identified for use in a wet or corrosive environment. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.