Violation Detail

Standard Cited: 19100303 G01 II General.

Inspection Nr: 1450220.015

Citation: 01005B

Citation Type: Serious

Abatement Status: Corrected During Inspection

Initial Penalty: $0.00

Current Penalty: $0.00

Issuance Date: 03/10/2020

Nr Instances: 1

Nr Exposed: 18

Abatement Date:

Gravity: 1

Report ID: 0112000

Contest Date:

Final Order: 04/06/2020

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 04/06/2020 $0.00   Serious  
Penalty Z: Issued 03/10/2020 $0.00   Serious  

Text For Citation: 01 Item/Group: 005B Hazard:

29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: PRODUCTION AREA OUTSIDE THE UT COMPOSITE ROOM: On or about December 12, 2019, old file cabinets were stored within 31 inches of the electrical panel labeled as "Distribution Panel 480/277V #8" and within 43 inches of the panel labeled "Lighting Panel (#9) 480/277V".

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close