Standard Cited: 19100307 C Hazardous (classified) locations.

This violation item has been deleted.

Inspection Nr: 1398632.015

Citation: 01005B

Citation Type: Willful

Abatement Status:  

Initial Penalty: $0.00

Current Penalty: $0.00

Issuance Date: 10/24/2019

Nr Instances: 1

Nr Exposed: 32

Abatement Date: 12/12/2019

Gravity: 10

Report ID: 0524200

Contest Date: 09/19/2019

Final Order: 11/08/2024

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty F: Formal Settlement 11/08/2024 $0.00 12/12/2019 Willful  
Penalty C: Contested 01/07/2020 $0.00 12/12/2019 Willful  
Penalty Z: Issued 10/24/2019 $0.00 12/12/2019 Willful  

Text For Citation: 01 Item/Group: 005B Hazard:

29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: The employer does not ensure that all equipment, wiring methods and installations of equipment are intrinsically safe, approved for hazardous (classified) locations or safe for use in the hazardous (classified) location. This condition most recently occurred from April 29, 2019 through May 3, 2019, where volatile flammable liquids were handled, processed, and used in reactor vessel S8. a) A DuraPulse Frequency Drive connected to an electric pump was used in a Class 1 Division 2 location in the area around reactor S8 during the period from April 29, 2019 through May 3, 2019. The DuraPulse Frequency Drive was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. b) A Delta T 144kW Oil Heater Model T1999CS was used in a Class 1 Division 2 location in the area around Reactor S8 during the period from April 29, 2019 through May 3, 2019. The reactors oil heater was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. c) The wiring for a Lightnin Agitator Motor located in a Class 1 Division 2 hazardous (classified) location on Reactor S8, and was in this location from April 29, 2019 through May 3, 2019, was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.