Violation Detail
Standard Cited: 19100334 D Use of equipment.
Inspection Nr: 1385559.015
Citation: 01005B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/22/2019
Nr Instances: 2
Nr Exposed: 6
Abatement Date: 09/18/2019
Gravity: 5
Report ID: 0213400
Contest Date:
Final Order: 09/18/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/18/2019 | $0.00 | 09/18/2019 | Serious | |
| Penalty | Z: Issued | 08/22/2019 | $0.00 | 09/18/2019 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.334(d): Where flammable materials were present only occasionally, such as but not limited to flammable gases, vapors, or liquids; combustible dust; and ignitable fibers or flyings, electrical equipment capable of igniting them were used and measures were not taken to prevent hazardous conditions from developing: a) 3 Terminal Road, New Brunswick, NJ - Tablet Press/Encapsulation Department Vacuums used to clean up Class II explosive dusts, were not intrinsically safe, approved for use in a Class II, Division 2 location or safe for a Class II, Division II location. Dusts which accumulated on the floors and on tablet press machine surfaces during the encapsulation process, had explosion severities of 1.81 and a Kst value of 22.72. Condition observed on or about 3/15/2019. WRITTEN ABATEMENT CERTIFICATION IS REQUIRED PURSUANT TO 29 CFR 1903.19.