Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
Inspection Nr: 998870.015
Citation: 01005A
Citation Type: Serious
Abatement Date: 04/08/2015 2
Initial Penalty: $5,000.00
Current Penalty: $3,500.00
Issuance Date: 03/17/2015
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 04/14/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/14/2015 | $3,500.00 | 04/08/2015 | Serious | |
Penalty | Z: Issued | 03/17/2015 | $5,000.00 | 04/08/2015 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.106(d)(4)(i): "Construction." Inside storage rooms were not constructed to meet the required fire-resistive rating for their use. Such construction did not comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. Where an automatic sprinkler system is provided, the system not designed and installed in an acceptable manner. Openings to other rooms or buildings were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area were not at least 4 inches below the surrounding floor. Openings were not provided with approved self-closing fire doors. The room was not liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp was not an open-grated trench inside of the room which drains to a safe location. Where other portions of the building or other properties are exposed, windows were not protected as set forth in the Standard for Fire Doors and Windows, NFPA No. 80-1968, which is incorporated by reference as specified in Sec. 1910.6, for Class E or F openings. Wood at least 1 inch nominal thickness was not used for shelving, racks, dunnage, scuffboards, floor overlay, and similar installations: a. On or about October 15, 2014, at the paint mix and storage trailer, there was no self-closing door for the opening to the paint building; there was no raised sill, ramp, or open-grated trench where the floor storage area was the same level throughout the trailer. Flammable liquids were stored such as coatings, primers, and thinners in excess of 120 gallons, which exposes employees to fire and explosion hazards.