Violation Detail
Standard Cited: 19100119 J02 Process safety management of highly hazardous chemicals.
Inspection Nr: 1708799.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $11,250.00
Issuance Date: 04/09/2024
Nr Instances: 5
Nr Exposed: 8
Abatement Date: 07/10/2024
Gravity: 10
Report ID: 0625700
Contest Date:
Final Order: 06/28/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/28/2024 | $11,250.00 | 07/10/2024 | Serious | |
| Penalty | Z: Issued | 04/09/2024 | $16,131.00 | 07/10/2024 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment. Instance a.) On or about 11/07/2023, at No. 4 Crude unit, the employer failed to ensure that written procedures for testing of Pressure Indication Control PIC-401 (P&ID 58-E-54-2003, No. 20) were established. Instance b). On or about 11/07/2023, at No. 1 Platformer unit, the employer failed to ensure that written procedures for testing of Hydrogen Low Flow Interlocks FT-7302A/B/C/D (P&ID 18-E-54-1000, No. 16) were established. Instance c). On or about 11/07/2023, at No. 1 Platformer unit, the employer failed to ensure that written procedures for testing of Level Indication Control LIC-7303 (P&ID 18-E-54-3000, No. 21) were established. Instance d). On or about 11/07/2023, at No. 1 Platformer unit, the employer failed to ensure that written procedures for testing of High-High Level Alarm (High Level Shutdown Switch) LAHH-7351 for No. 1 Platform Product Separator, 18-SE-01 (P&ID 18-E-54-3000, No. 21) were established. Instance e). On or about 11/07/2023, at No. 1 Platformer unit, the employer failed to ensure that written procedures for testing of the emergency remote shutdown HS-7370A of Platformer East Compressor, C-0010, (P&ID 18-E-54-5000G, No. 1) were established.
Translate