Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1401850.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,304.00
Current Penalty: $2,500.00
Issuance Date: 10/29/2019
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 11/20/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/20/2019 | $2,500.00 | Serious | ||
Penalty | Z: Issued | 10/29/2019 | $5,304.00 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) Trailer Shop - Against the back corner of the East Facing wall, 1040 North Brewster Road, Vineland NJ: On or about 05/17/19 circuit breakers were frequently used as switches, controlling the power to the Trailer Shop's lighting. As such, these circuit breakers were not being used as per their manufacturer's requirements and were not listed or marked "SWD".