Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1385559.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,229.00
Current Penalty: $7,760.00
Issuance Date: 08/22/2019
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 09/18/2019
Gravity: 5
Report ID: 0213400
Contest Date:
Final Order: 09/18/2019
Related Event Code (REC):
Emphasis:
Substance: E100
Substance: M102
Substance: M104
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/18/2019 | $7,760.00 | 09/18/2019 | Serious | |
| Penalty | Z: Issued | 08/22/2019 | $10,229.00 | 09/18/2019 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.307(c): Electrical equipment in a hazardous (classified) location was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) 3 Terminal Road, New Brunswick, NJ - Tablet Press/Encapsulation Department/Individual rooms Electrical installations including, but not limited to, 20 amp/GFI/GFNT2 and 20 amp/250 volt duplex rec/Industrial Grade/5462 (outlet receptacles) used for plugging in tablet press machines, were not intrinsically safe, explosion proof, approved for Class II, Division 2 locations or safe for a Class II, Division II location. Dusts which accumulated on the floors and on tablet press machine surfaces during the encapsulation process, had explosion severities of 1.81 and a Kst value of 22.72. Condition observed on or about 3/15/2019. WRITTEN ABATEMENT CERTIFICATION IS REQUIRED PURSUANT TO 29 CFR 1903.19.
Translate