Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 1383731.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $6,819.00
Current Penalty: $3,409.50
Issuance Date: 08/08/2019
Nr Instances: 4
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0524500
Contest Date:
Final Order: 08/27/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/27/2019 | $3,409.50 | Serious | ||
| Penalty | Z: Issued | 08/08/2019 | $6,819.00 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: On or about March 8, 2019, employees were exposed to electrical hazards because: a) the Square D Disconnect labeled 208 located in the Maintenance Shop was missing a knockout. b) the outlet box located beneath the Square D Disconnect labeled 208 located in the Maintenance Shop was missing a knockout. c) the electrical panel marked HOL located in the Main Electrical Distribution Room contained unused openings at breakers 2, 4, 6 and 18. d) the electrical panel marked TR located in the Main Telecommunications Distribution Room contained unused openings at breakers 39 through 42.