Violation Detail
Standard Cited: 19100107 C05 Spray finishing using flammable and combustible materials.
Inspection Nr: 1345312.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,956.00
Current Penalty: $1,478.00
Issuance Date: 11/29/2018
Nr Instances: 2
Nr Exposed: 14
Abatement Date: 01/31/2019
Gravity: 5
Report ID: 0522300
Contest Date:
Final Order: 12/26/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/26/2018 | $1,478.00 | 01/31/2019 | Serious | |
Penalty | Z: Issued | 11/29/2018 | $2,956.00 | 12/14/2018 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.107(c)(5): In areas with combustible residues, the employer did not ensure there was no electrical equipment in any spraying area, whereon deposits of combustible residues may readily accumulate: a) On or about September 10, 2018, the employer had installed an electrical powered mounted drill in the paint spray booth that was not approved for Class I, group D locations. The powered drill had residue build up that was found to be ignitable. b) On or about September 10, 2018, the employer had installed uncovered fluorescent light fixtures in the powder coating spray booth that was not approved for Class I, group D locations. The light fixtures were exposed and had residue build up that was found to be ignitable.