Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1157891.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,237.00
Current Penalty: $6,237.00
Issuance Date: 11/15/2016
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 12/30/2016
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 12/05/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/05/2016 | $6,237.00 | 12/30/2016 | Serious | |
| Penalty | Z: Issued | 11/15/2016 | $6,237.00 | 12/30/2016 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment: This violation was most recently observed on or about June 21, 2016 and times thereafter, in the Ammonia Refrigeration Process at American Cold Storage located in Tulsa, Oklahoma when the employer failed to perform inspections and tests on the thirteen Ammonia detectors (Honeywell) and alarms located in the machine room, freezers, cooler and dock area.