Violation Detail
Standard Cited: 19100303 B06 General.
Inspection Nr: 1084449.015
Citation: 01005A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,500.00
Current Penalty: $2,275.00
Issuance Date: 12/18/2015
Nr Instances: 2
Nr Exposed: 7
Abatement Date: 02/29/2016
Gravity: 5
Report ID: 0317500
Contest Date:
Final Order: 01/13/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/13/2016 | $2,275.00 | 02/29/2016 | Serious | |
Penalty | Z: Issued | 12/18/2015 | $3,500.00 | 01/15/2016 | Serious |
Text For Citation: 01 Item/Group: 005A Hazard:
29 CFR 1910.303(b)(6): Electrical equipment were exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment: a) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084: On or about July 28, 2015, graphite dust accumulated on and inside of the #2 press motor control center. The #2 press motor control cabinet was labeled as a HRC Level 4 arc flash and shock hazard. Press operators, electricians, forklift operators, and laborers working in the area of the #2 press PLC cabinet were exposed to the hazards of arc flash, electric shock and electrocution. b) K-Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084: On or about July 28, 2015, a significant amount of graphite dust accumulated inside the '2C' panel on the #1 Press motor control cabinet. This panel was left open due to a broken clip. The #1 Press motor control center houses 480 volt, 3 phase conductors and was labeled as a HRC Level 4 arc flash and shock hazard. Press operators, electricians, forklift operators, and laborers working in the area of the #1 press motor control cabinet were exposed to the hazards of arc flash, electric shock and electrocution.