Violation Detail
Standard Cited: 19100178 G02 Powered industrial trucks.
Inspection Nr: 984505.015
Citation: 01005
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $3,080.00
Current Penalty: $1,000.00
Issuance Date: 01/06/2015
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 02/24/2015
Gravity: 5
Report ID: 0112000
Contest Date: 07/06/2020
Final Order: 07/06/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 07/30/2020 | $3,080.00 | 02/24/2015 | Serious | |
Penalty | F: Formal Settlement | 07/06/2020 | $1,000.00 | 02/24/2015 | Serious | |
Penalty | Z: Issued | 01/06/2015 | $3,080.00 | 02/24/2015 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.178(g)(2): Facilities were not provided for flushing and neutralizing spilled electrolyte, for fire protection, for protecting charging apparatus from damage by trucks, and/or for adequate ventilation for dispersal of fumes from gassing batteries. PIV CHARGING STATION/VICINITY OF PANEL LPL On or about July 10, 2014, the employer did not take measures to protect the battery chargers for the powered industrial vehicles/fork trucks from damage by the trucks. In addition, there was no quick flush shower or eye wash for neutralizing battery acid. The battery chargers were located at the base of the column on which Electrical Panel LPL is mounted with no barriers to prevent collisions from occurring.