Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 L01 Process safety management of highly hazardous chemicals.

Inspection Nr: 960754.015

Citation: 01005

Citation Type: Other

Abatement Status: Abatement Completed

Initial Penalty: $6,000.00

Current Penalty: $6,000.00

Issuance Date: 08/27/2014

Nr Instances: 11

Nr Exposed: 10

Abatement Date: 09/11/2015

Gravity:

Report ID: 0729700

Contest Date: 09/22/2014

Final Order: 09/24/2015

Related Event Code (REC): C

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty C: Contested 10/23/2015 $6,000.00 10/10/2014 Serious  
Penalty F: Formal Settlement 09/24/2015 $6,000.00 09/11/2015 Other  
Penalty Z: Issued 08/27/2014 $6,000.00 10/10/2014 Serious  

Text For Citation: 01 Item/Group: 005 Hazard:

29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process: At the facility the employer had not implemented the management of change program to address changes to the Ammonia process; there has been several changes to the processes such as but not limited to the following: (a) for the removal of insulation from shut-off valve (6-L-407) on the 6-HTRL-5640-XR pipe line. (V-10002) (b) for the removal of insulation from valve (½-G-417) on an unidentified pipe line. (V-10002) (c) for the removal of insulation from valve (½-G-536) on an unidentified pipe line. (V-30001) (d) for the removal of insulation from valve (6-L-273) on the 6-HTRL-5613-XR pipe line. (e) for the removal of insulation from valve (¾-G-294) on unidentified pipe line. (V-10001) (f) for the removal of insulation from valve (6-L-271) on unidentified pipe line. (V-10001) (g) for the removal of insulation from the drain down valve (1-G-605) on unidentified pipe line. (V-30002) (h) for the removal of insulation from the liquid pump valve (1-L-612) on the 1-ODR-8005-XR pipe line. (V-30002) (i) for the removal of insulation from the liquid pump valve (4-L-623) on the 4-LLTRL-6754-XR piping. (V-30002) (j) for the removal of insulation from the 2-LTL-5806-XR low liquid ammonia piping between valves 2-G-606 AND 2-E-608. (V-30002) (k) the addition of a check valve and padlocked globe valve to the ammonia charge line inlet area. Employee(s) were exposed to release of ammonia vapor / liquid to the atmosphere that historically results in health hazards leading to injury and death to persons in the workplace.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.