Violation Detail
Standard Cited: 19100119 E03 I Process safety management of highly hazardous chemicals.
Inspection Nr: 922655.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,500.00
Current Penalty: $2,100.00
Issuance Date: 01/21/2014
Nr Instances: 3
Nr Exposed: 92
Abatement Date: 02/28/2014
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 02/07/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/07/2014 | $2,100.00 | 02/28/2014 | Serious | |
| Penalty | Z: Issued | 01/21/2014 | $3,500.00 | 02/14/2014 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.119(e)(3)(i): The PHA did not address the hazards of the process. a) Furnace area: The employer's PHA did not address the potential release of chlorine during removal of the angle tube gas injection pump and motor, on or about 7/23/13. b) Chlorine room: The employer's PHA did not address failure of the interlocks, namely the gas pressure reducing valve sensor for the evaporators and the Halogen Valve Systems Eclipse Actuator connected to the cylinder, on or about 7/23/13.