Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 427054.015
Citation: 01005
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,000.00
Current Penalty: $4,250.00
Issuance Date: 11/13/2012
Nr Instances: 1
Nr Exposed: 4
Abatement Date:
Gravity: 5
Report ID: 0316400
Contest Date:
Final Order: 12/11/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/11/2012 | $4,250.00 | Serious | ||
| Penalty | Z: Issued | 11/13/2012 | $5,000.00 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a)Third Floor, Breaker Panel: A three phase 120/208 volt Westinghouse Electric Corporation circuit breaker box had an opening measuring 11 inches in length by 1 and ? inches in height. The opening was not effectively closed to prevent employee contact with the energized bus bar, as determined on May 14, 2012. Abatement Certification Required for this Item