Violation Detail
Standard Cited: 19100119 J04 II Process safety management of highly hazardous chemicals.
Inspection Nr: 314511064
Citation: 01005
Citation Type: Serious
Abatement Date: 10/09/2012 X
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 09/13/2012
Nr Instances: 4
Nr Exposed: 10
Related Event Code (REC):
Gravity: 10
Report ID: 0855610
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/02/2012 | $7,000.00 | 10/09/2012 | Serious | |
Penalty | Z: Issued | 09/13/2012 | $7,000.00 | 10/09/2012 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard: REFINERY
1910.119(j)(4)(ii)* Inspection and testing. Inspection and testing procedures shall follow recognized and generally accepted good engineering practices: LPG Bullet pressure vessels not being inspected following recognized and generally accepted good engineering practices identified in API Standard 653. Tanks/vessels were not being inspected within 10 years of initial placement into service. Ancillary Reference: API Standard 653, 4th Edition, April 2009. 6.1 General - Periodic in- service inspection of tanks shall be performed as defined herein. The purpose of this inspection is to assure continued tank integrity. 6.4.4.4 Internal inspection is primarily required to do as follows. c) Identify and evaluate any tank bottom settlement. 6.4.2.1 The interval from initial service until the initial internal inspection shall not exceed 10 years.