Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 190507.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,000.00
Current Penalty: $1,200.00
Issuance Date: 04/13/2012
Nr Instances: 5
Nr Exposed: 13
Abatement Date: 06/01/2012
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 05/09/2012
Related Event Code (REC):
Emphasis:
Substance: E101
Substance: E200
Substance: M102
Substance: M104
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/09/2012 | $1,200.00 | 06/01/2012 | Serious | |
| Penalty | Z: Issued | 04/13/2012 | $3,000.00 | 05/13/2012 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a. In the mill corn bagging area near the DCE Unimaster dust collector (model: 102-K3) and the 3 ton Blue Streak Twin Spiral vertical mixer, electrical equipment including, but not limited to, the duplex receptacle, snap switch for outside light, and snap switch for inside lights in a Class II, Division 2 location were not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location. d. In the bagging area near the Big Chief cracker and Creamer inside elevator legs, electrical equipment including, but not limited to, the Doron digital scale (model: 8000) plugged into a duplex receptacle, snap switch, and 220 VAC receptacle in a Class II, Division 1 location were not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location.
Translate