Violation Detail
Standard Cited: 19100107 C02 Spray finishing using flammable and combustible materials.
Inspection Nr: 1808803.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,513.00
Current Penalty: $4,256.50
Issuance Date: 07/22/2025
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 08/25/2025
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 08/27/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/27/2025 | $4,256.50 | 08/25/2025 | Serious | |
| Penalty | Z: Issued | 07/22/2025 | $8,513.00 | 08/25/2025 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.107(c)(2): There shall be no open flame or spark producing equipment in any spraying area nor within 20 feet thereof, unless separated by a partition. a. Located in the Color Lab: On or about March 6, 2025, Spray Booth #6 was located within approximately 14" of the lab's electric drying rack, which created a potential fire hazard based on errant sparks and/or radiant heat. b. Located in the Blending Room: On or about March 6, 2025, Spray Booth #2 was located approximately 53" from the room's electric drying rack, which created a potential fire hazard based on errant sparks and/or radiant heat.
Translate