Violation Detail
Standard Cited: 19100147 C04 II The control of hazardous energy (lockout/tagout).
Inspection Nr: 1582355.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,801.00
Current Penalty: $2,500.00
Issuance Date: 08/16/2022
Nr Instances: 1
Nr Exposed: 16
Abatement Date: 10/03/2022
Gravity: 5
Report ID: 0830500
Contest Date:
Final Order: 09/08/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/08/2022 | $2,500.00 | 10/03/2022 | Serious | |
Penalty | Z: Issued | 08/16/2022 | $5,801.00 | 10/03/2022 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.147(c)(4)(ii): The energy control procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy: (a) On or about March 7, 2022, and at times prior, the procedure for controlling the energy of machines including but not limited to conveyers, the brewhouse pump, can filler, can depalletizer, cellar pump, filter pump, the HLT and HLT pump, lauter tun, mash tun, and the mill and auger, did not have specific information for each machine or machine type, including: the type and magnitude of energies, the hazards to be controlled and the methods or means that will be used to control the energies, machine specific shut down steps, how and where to isolate the machine(s) from energy sources, including placement of isolation devices, how to place locks (and/or tags) on each energy isolating device, bleeding, blocking, or other steps to addressed stored and reaccumulating energy, and testing to verify isolation. This condition exposed workers to hazards of unexpected energization while performing servicing and maintenance.