Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1580830.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,188.00
Current Penalty: $8,000.00
Issuance Date: 08/26/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 12/30/2022
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 10/12/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/12/2022 | $8,000.00 | 12/30/2022 | Serious | |
Penalty | Z: Issued | 08/26/2022 | $11,188.00 | 10/14/2022 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.303(g)(1)(i): Workspace was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: Maintenance Room - First Floor: On or about April 21, 2022, and at times thereafter, workspace was less than 30 inches wide when maintenance had to access the control panel and disconnect switch for the main exhaust, which were located on the second floor in the mechanical room. The equipment was obstructed by stacks of items that were adjacent to the panel and switch, which were approximately five inches in distance from the access points.