Violation Detail
Standard Cited: 19100157 D01 Portable fire extinguishers.
This violation item has been deleted.
Inspection Nr: 1559816.015
Citation: 01005
Citation Type: Serious
Abatement Status: Not Completed - AD Discretion
Initial Penalty: $9,324.00
Current Penalty: $0.00
Issuance Date: 04/11/2022
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 05/16/2022
Gravity: 5
Report ID: 0830500
Contest Date:
Final Order: 05/11/2022
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/11/2022 | $0.00 | 05/16/2022 | Serious | |
| Penalty | Z: Issued | 04/11/2022 | $9,324.00 | 05/16/2022 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.157(d)(1): Portable fire extinguishers were not selected based on the classes of anticipated workplace fires and on the size and degree of hazard that would affect their use: a) Boulder Scientific Company, LLC., 598 Third Street, Mead, CO 80542: On or about October 22, 2021, the fire extinguishers used to try to extinguish the fire were Class ABC extinguishers instead of Class D, which were not suitable for fires that are associated with pyrophoric chemicals. The chemicals used in this room, butyl lithium and lithium hydride were water reactive. While in the process of trying to contain an incipient stage fire employees were unable to put out the fire out until soda ash/ dry chemicals were used. The employee, as well as, other in the immediate area were not protected from fire hazards.