Violation Detail
Standard Cited: 19100335 A02 I A Safeguards for personnel protection.
Inspection Nr: 1456731.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,494.00
Current Penalty: $9,459.97
Issuance Date: 07/06/2020
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 07/30/2020
Gravity: 10
Report ID: 0524200
Contest Date: 07/29/2020
Final Order: 04/12/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/12/2021 | $9,459.97 | 07/30/2020 | Serious | |
Penalty | C: Contested | 09/14/2020 | $13,494.00 | 07/30/2020 | Serious | |
Penalty | Z: Issued | 07/06/2020 | $13,494.00 | 07/30/2020 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.335(a)(2)(i)(A): Fuse handling equipment, insulated for the circuit voltage, was not used to remove or install fuses when fuse terminals were energized: a) Kitchen 5 - On or about January 9, 2020, the employer failed to ensure that employees working in areas where there was the potential for electrical hazards inside the 480 Volt MCC Panels in Kitchen 5 were using only fuse handling equipment that was insulated for the circuit voltage when removing and installing fuses. b) Production Area - On or about January 21, 2020, the employer failed to ensure that employees working in areas where there was the potential for electrical hazards inside the 480 Volt MCC Panels in Mogul 7 were using only fuse handling equipment that was insulated for the circuit voltage when removing and installing fuses. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.