Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.

Inspection Nr: 1390220.015

Citation: 01005

Citation Type: Serious

Abatement Status: Not Completed - Employer Out of Business

Initial Penalty: $11,934.00

Current Penalty: $11,934.00

Issuance Date: 09/30/2019

Nr Instances: 4

Nr Exposed: 24

Abatement Date: 01/02/2020

Gravity: 10

Report ID: 0626600

Contest Date: 10/22/2019

Final Order: 12/28/2020

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty W: Empr Withdrew 12/28/2020 $11,934.00 01/02/2020 Serious  
Penalty C: Contested 10/22/2019 $11,934.00 01/02/2020 Serious  
Penalty Z: Issued 09/30/2019 $11,934.00 01/02/2020 Serious  

Text For Citation: 01 Item/Group: 005 Hazard:

1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On or about 04/02/19, at the KMCO facility located in Crosby Texas, the employer did not document that equipment complied with recognized and generally accepted good engineering practice such as America Petroleum Institute (API) 521- 2007 Edition (Pressure-relieving and De-pressuring Systems) when it failed to ensure that pressure relief valve stacks that discharge to the atmosphere at least 15 meters (50 feet) horizontally from any structures for the following but not limited to: a) PSV-165 (or RV-17340) stack which protects isobutylene pressure vessel (T-2503) as depicted on New IB storage P&ID (Drawn 10/26/16) b) PSV-164 (or RV-17339) stack which protects isobutylene pressure vessel (T-2503) as depicted on New IB storage P&ID (Drawn 10/26/16) c) SRV- 4376 (or RV-21658) stack which protects propylene oxide pressure vessel (T-2010) as depicted PO Storage P&ID PG.1 (Drawn 11/23/16) d) SRV- 4375 stack which protects propylene oxide pressure vessel (T-2010) as depicted PO Storage P&ID PG.1 (Drawn 11/23/16) This condition exposes workers to the hazards of a catastrophic equipment failure including being struck by a high energy release, equipment parts and fire/explosion.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.