Violation Detail
Standard Cited: 19100107 L01 Spray finishing using flammable and combustible materials.
Inspection Nr: 1318784.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,239.00
Current Penalty: $5,173.84
Issuance Date: 10/16/2018
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 02/08/2019
Gravity: 5
Report ID: 0418100
Contest Date:
Final Order: 11/01/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/01/2018 | $5,173.84 | 02/08/2019 | Serious | |
Penalty | Z: Issued | 10/16/2018 | $9,239.00 | 12/04/2018 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.107(l)(1): Electrical equipment and other sources of ignition did not conform to the requirements of paragraphs (c)(1)(i)-(iv), (8) and (9)(i) of this section and subpart S of this part: Southern Tire Mart, Covington, GA - On or about May 29, 2018, and times prior to, powder coating was conducted with portable hand spraying equipment in a spraying area. Electrical wiring, electrical outlets and electric fans used in the area were not approved for hazardous location type as required by Subpart S. The employer failed to use approved electrical equipment with in 5 feet (Class II, Division 1) and 20 feet (Class II, Division 2) areas. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).