Violation Detail
Standard Cited: 19100137 C02 VIII Electrical protective equipment.
Inspection Nr: 1255862.015
Citation: 01005
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,315.00
Current Penalty: $4,989.00
Issuance Date: 01/29/2018
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 04/30/2018
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 02/21/2018
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | P: Petition to Mod Abatement | $4,989.00 | 04/30/2018 | Serious | ||
| Penalty | I: Informal Settlement | 02/21/2018 | $4,989.00 | 03/30/2018 | Serious | |
| Penalty | Z: Issued | 01/29/2018 | $8,315.00 | 02/16/2018 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5. a. On or about August 23, 2017, located in the motor room, employees wore rubber insulated gloves while performing electrical work that had not been electrically tested within the last six months, thereby exposing the employees up to an electrical shock hazard of 13,800 VAC.