Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1161318.015
Citation: 01005
Citation Type: Serious
Abatement Date: 01/10/2017 2
Initial Penalty: $6,236.00
Current Penalty: $5,000.00
Issuance Date: 11/15/2016
Nr Instances: 2
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0418600
Contest Date:
Final Order: 12/08/2016
Emphasis:
Substance: E200
Substance: G109
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/08/2016 | $5,000.00 | 01/10/2017 | Serious | |
Penalty | Z: Issued | 11/15/2016 | $6,236.00 | 11/23/2016 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) Building 2- Gluten Mill Area: On or about July 12, 2016, and at times prior to, the employer exposed employees to explosion hazards due to non-class II rated electrical boxes installed by dust collection systems near the Engsko Milling System Horizontal Grain Mill were not effectively closed. a) Building 2- Gluten Free Mill Area: On or about July 12, 2016, and at times prior to, the employer exposed employees to explosion hazards due to non-class II rated electrical boxes installed by dust collection systems near the Meadows Horizontal Corn Milling machine were not effectively closed.