Violation Detail
Standard Cited: 19100253 B04 III Oxygen-fuel gas welding and cutting.
Inspection Nr: 1128504.015
Citation: 01005
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $1,200.00
Current Penalty: $780.00
Issuance Date: 07/26/2016
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 1
Report ID: 0316400
Contest Date:
Final Order: 08/11/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/11/2016 | $780.00 | Serious | ||
| Penalty | Z: Issued | 07/26/2016 | $1,200.00 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: (a) Compressed Gas Storage Area, Back of Shop: On March 3, 2016 and times prior, the employer did not ensure that oxygen cylinders were separated from acetylene cylinders by at least 20 feet or a 5 foot noncombustible barrier. Two acetylene cylinders were stored 13 feet from three oxygen cylinders.