Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 314198375
Citation: 01004E
Citation Type: Serious
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 08/09/2010
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 09/23/2010
Gravity: 10
Report ID: 0418300
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
Substance: 0170
Text For Citation: 01 Item/Group: 004E Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: e) On or about February 24, 2010 - ammonia machine room, examination for compressor vibration was performed only by visual observation and hand touch and not in accordance with IIAR Bulletin 110, 1993 Section 6.3.2.