Violation Detail
Standard Cited: 19101000 E Air contaminants.
Inspection Nr: 1680792.015
Citation: 01004E
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/21/2023
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 05/06/2024
Gravity: 10
Report ID: 0317900
Contest Date: 01/05/2024
Final Order: 05/01/2024
Related Event Code (REC):
Emphasis:
Substance: 9130
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 05/01/2024 | $0.00 | 05/06/2024 | Other | |
Penalty | C: Contested | 02/28/2024 | $0.00 | 05/06/2024 | Serious | |
Penalty | Z: Issued | 12/21/2023 | $0.00 | 05/06/2024 | Serious |
Text For Citation: 01 Item/Group: 004E Hazard:
29 CFR 1910.1000(e): Feasible administrative or engineering controls were not determined and implemented to achieve compliance with the limits prescribed in 29 CFR 1910.1000(a) through (d): a) Oldcastle APG Northeast - On or about July 7, 2023, a Bagger working on line 5, was exposed to an 8 hour time weighted average of 7.42 mg of Respirable Particulates Not Otherwise Regulated (PNOR) per cubic meter of air. This exposure is 1.477 times the permissible exposure limit (PEL) of 5 milligrams per cubic meter (mg/m�) of air . This exposure occurred over a 460 minute sampling period. A zero exposure was assumed for the 25 minutes not sampled. The employer did not implement feasible engineering or administrative controls to reduce employee exposure to PNOR below the PEL. Feasible abatement methods include but are not limited to: 1) Improve or redesign the physical structure and/or ventilation draw of the ductwork to increase CFM and capture velocity. 2) Administratively reduce exposure time by rotating employees to other jobs in the facility instead of spending their entire shift bagging. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photograph or video evidence of abatement or other written records.