Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 314198375
Citation: 01004D
Citation Type: Serious
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 08/09/2010
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 09/23/2010
Gravity: 10
Report ID: 0418300
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
Substance: 0170
Text For Citation: 01 Item/Group: 004D Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: d) On or about February 24, 2010 - the employer did not ensure that the discharge from the relief valve to atmosphere on the ammonia system receiver vented at least 15 feet above grade as required by IIAR Standard 2-2008, Section 11.3.6.4.