Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.

Inspection Nr: 314198375

Citation: 01004D

Citation Type: Serious

Abatement Status: X

Initial Penalty:

Current Penalty:

Issuance Date: 08/09/2010

Nr Instances: 1

Nr Exposed: 4

Abatement Date: 09/23/2010

Gravity: 10

Report ID: 0418300

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:

Substance: 0170



Text For Citation: 01 Item/Group: 004D Hazard: CHEMNEP

29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: d) On or about February 24, 2010 - the employer did not ensure that the discharge from the relief valve to atmosphere on the ammonia system receiver vented at least 15 feet above grade as required by IIAR Standard 2-2008, Section 11.3.6.4.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.